Frequently Asked Question

Modbus Async network high busy times (Inter Message Delay)
Last Updated 10 years ago

When using the Niagara Modbus Async driver, we have found that the default setting of 0 on the inter message delay causes high busy times when doing a number of read/write actions.Putting a setting in with a minimum of 20ms has found that the read/write actions do not then create a high busy time on the network.

image

This value may need adjusting for individual networks, but should not be left at 0 if problems are being experienced on networks.